www.baumer.com
CombiView
™
DFON display
There are 9 different display modes available
Digital Analogue Bar graph Tank
small analogue horizontal tank illustration
large same w. bar graph vertical bottle illustration
same w. value
Electrical connection
Pin 1 + 4…20 mA (not connected)
Pin 2 - 4…20 mA (not connected)
Pin 3 Relay 1
Pin 4 Relay 1
Pin 5 Relay 2
Pin 6 Relay 2
Com 1 FlexProgrammer ① red
Com 2 FlexProgrammer ② black
The PFMx with DFON display is delivered with terminal 1 and 2 not connected. The DFON is powered and will have data direct
through a special ribbon cable (UnitCom). Via UnitCom the DFON and PFMx transmitter can be programmed together when con-
necting the FlexProgrammer to Com 1 and COM 2 on the back of the display.
Pin 3 and 5 can be jumpered together if common supply is used for the two relays, e.g. via a M12 5-pin connector. Two galvanic
separated relay outputs will require a 8-pin M12 connector if plug connection is required. If cable glands is used the terminals 4...6
is connected via the screw terminals.
Electrical connection
Operators instructions
CombiPress™, type PFMx
UnitCom
Operators instructions: 11120948 PFMx Page 5 / 12
Electrical connection
M12, 5-wire M12, 8-wire
1 + supply, 4...20 mA 1 n.c.
2 Common for relays 2 + supply, 4...20 mA
3 - supply, 4...20 mA 3 Relay 1
4 Relay 1 4 Relay 1
5 Relay 2 5 Relay 2
6 Relay 2
7 - supply, 4...20 mA
8 n.c.
Cable gland
Transmitter
- - supply, 4...20 mA
+ + supply, 4...20 mA
Com 1 Red clip (FlexProgrammer)
Com 2 Black clip (FlexProgrammer)
Display
1 n.c.
2 n.c.
3 Relay 1
4 Relay 1
5 Relay 2
6 Relay 2
Com 1 Red clip (FlexProgrammer)
Com 2 Black clip (FlexProgrammer)