5 Technical data
Technical data - electrical ratings
Voltage supply 21...53 VAC (50/60 Hz) or
10.5...70 VDC
85...265 VAC (50/60 Hz) or
100...300 VDC
Power consumption 2.2 W
Sensor supply 5 V, 8 V or 12 V
programmable/60 mA
Display LED, 7-segment display (with 60 unit
stickers for front)
Number of digits 4-digits
Digit height 10 mm
Display range 9999 („OuE“ to signal overflow)
Display refresh 0.1... 9.9 s (programmable)
Programmable Measuring units 1/h, 1/min, 1/s
parameters Sensor logic
Decimal point
Sensor supply
Impulse evaluation
Measuring principle Period duration measurement
Signal inputs Programmable as NPN, PNP, Namur,
TTL, 10...600 VAC or contact
Counting frequency 0.01 Hz...7 kHz (20 Hz if contact input)
Data memory >10 Jahre in EEPROM
Standard Protection class II
DIN EN 61010-1 Overvoltage category II
Pollution degree 2
Emitted interference DIN EN 61000-6-3
Interference immunity DIN EN 61000-6-2
Technical data - mechanical design
Ambient temperature -10...+60 °C
Storing temperature -25...+85 °C
Relative humidity 95 % non-condensing
Connection Spring-loaded terminal connector,
detachable
Core cross-section 1 mm² (grid 2.54)
2.5 mm
2
(grid 7.62)
Protection DIN EN 60529 IP 65 (face)
Operation / keypad 3 softkeys below bezel
Housing type Built-in housing
Dimensions W x H x L 48 x 24 x 106 mm
Mounting Front panel installation by clip frame
Material Housing: Polycarbonate, UL 94V-0
Weight approx. 50 g