Bedienungsanleitung_Series09-US_RS232_V1_e.doc 4/11 Baumer Electric AG
26.03.2013 14:43:00/tof Frauenfeld, Switzerland
3 The RS-232 interface
3.1
General notes
Step 1: Setting of the sensitivity mode A-D; Step 2: Teaching of the Scanning range
In measuring mode: Yellow LED flashing = weak signal received. Conceivable corrective measures: teach
object anew; move object closer to sensor; clean transducer.
In measuring mode: Red LED on = object within blind range
Provided the Teach-in sequence cannot be successfully completed the sensor defaults automatically to the
previously saved settings.
Power must be switched off before connecting the sensors.
A soiled beam columnator may generate erroneous output signals. Therefore it must be checked from time
to time and cleaned if necessary.
Via the RS 232 interface measured data can be received and a number of functions are configurable.
The sensors work with a baud rate of 115’200
3.2 Structure of commands
All commands consist of ASCII characters only. One character consists of 1 start-Bit, 8 data-Bits and 1 Stop-
Bit.
Address
Address „0“ is the broadcast address, which is accepted by every sensor and which must be used when
using RS232.
Telegram sent by the control to the sensor:
{0AB}
NO CHECKSUM!
Telegram (sensor response) sent from the sensor to the control:
{0AB47}
For examples refer to chapter "3.8 Examples".
Address 1 number 0...8,
for RS232 always 0
Command
Character (A..Z)
Start of Frame (SOF)
X characters
(depends on the command)
End of Frame (EOF)
Address 1 number
0...8, for RS232
always 0
Command
Character (A..Z)
Start of Frame (SOF)
X characters
(depends on command)
End of Frame (EOF)
Checksum 2 Byte, see appendix